Passive Components
Description
Colored Single Wire Cable PVC Insulation Wire 70℃ Max Conductor Temperature
?
Descriptions
Single-core non-sheathed cables with rigid conductor for general purposes
Code designation: 60227 IEC 01 (International), BV (China), H07V-U(VDE)
?
? ? ? Constructions
? ? ? ? ① ? ?Conductor: Plain circular solid copper conductor, comform to IEC 60228 class 1
③ ? Conductor: Plain circular stranded copper conductor, comform to IEC 60228 class 2
② ? Insulation: PVC/C
?
Applications
In dry rooms, apparatus switch and distribution boards, for fixed installation in conduits, over and under plaster and on insulated supports over plaster. Direct laying in plaster is not permitted.
Standards
International: IEC 60227
China: GB/T 5023-2008
Other standards such as BS,DIN and ICEA upon request
?
Technical data
Rated voltage: 450/750 V
Max. Conductor Temp. in normal use: 70℃
Min. Bending Radius: 4 x cable O.D
Certificates
CE, RoHS, CCC, KEMA and more others at request
?
Specifications
?
BV300/500V
?
?
- - - -
Nominal area of conductor | No./Dia. Of Conductor | Max.O.D | Approx.Weight | Max. D.C Resistance of Conductor (20 ℃)Ω /km |
mm2 | mm | mm2 | kg/km | Ω /km |
0.5 | 1/0.80 | 2.3 | 8.5 | 36.0 |
0.75(A) | 1/0.97 | 2.5 | 11.1 | 24.5 |
0.75(B) | 7/0.37 | 2.6 | 12.0 | 24.5 |
1.0(A) | 1/1.13 | 2.7 | 13.9 | 18.1 |
1.0(B) | 7/0.43 | 2.8 | 15.0 | 18.1 |
- - - -
BV / BLV (BV-105) 450/750V
- - - -
Nominal area of conductor | No./Dia. Of Conductor | Max.O.D | Approx.Weight | Max. D.C Resistance of Conductor (20 ℃)Ω /km |
mm2 | mm | mm2 | kg/km | Ω /km |
Copper | Aluminium | Aluminium | Copper |
1.5(A) | 1/1.38 | 3.2 | 20.3 | ? | ? | 12.1 |
1.5(B) | 7/0.52 | 3.3 | 21.6 | ? | ? | 12.1 |
2.5(A) | 1/1.78 | 3.9 | 31.6 | 17 | 11.8 | 7.41 |
2.5(B) | 7/0.68 | 4.0 | 34.8 | 7.41 |
4(A) | 1/2.55 | 4.4 | 47.1 | 22 | 7.39 | 4.61 |
4(B) | 7/0.85 | 4.6 | 50.3 |
- - - -
?
BV/BLV(BV-105) 450/750V
?
- - - -
Nominal area of conductor | No./Dia. Of Conductor | Max.O.D | Approx.Weight | Max. D.C Resistance of Conductor (20 ℃)Ω /km |
mm2 | mm | mm2 | kg/km | Ω /km |
Copper | Aluminium | Aluminium | Copper |
6(A) | 7/0.85 | 5.0 | 50.3 | 29 | 4.91 | 3.08 |
6(B) | 7/1.04 | 5.2 | 71.2 | 29 | 4.91 | 3.08 |
10 | 7/1.35 | 6.4 | 119 | 62 | 3.08 | 1.83 |
16 | 7/1.70 | 7.8 | 179 | 78 | 1.91 | 1.15 |
25 | 27/2.04 | 9.7 | 281 | 118 | 1.20 | 0.727 |
35 | 27/2.52 | 10.9 | 381 | 156 | 0.868 | 0.524 |
50 | 19/1.78 | 12.8 | 521 | 215 | 0.641 | 0.387 |
70 | 19/2.14 | 14.4 | 734 | 282 | 0.443 | 0.268 |
95 | 19/2.52 | 17.1 | 962 | 385 | 0.320 | 0.193 |
120 | 37/2.03 | 18.8 | 1180 | 431 | 0.253 | 0.153 |
150 | 37/2.25 | 20.9 | 1470 | 539 | 0.206 | 0.124 |
185 | 37/2.52 | 23.3 | 1810 | 666 | 0.164 | 0.0991 |
240 | 61/2.25 | 26.6 | 2350 | 857 | 0.125 | 0.0754 |
300 | 61/2.52 | 29.6 | 2930 | 1070 | 0.100 | 0.0601 |
400 | 61/2.85 | 33.2 | 3870 | 1390 | 0.0778 | 0.0470 |
- - - -
?
Read More
Shanghai Shenghua Cable (Group) Co., Ltd.
XLPE Insulated Power Cable,Armoured Electrical Cable,PVC Insulated Cables
Address: No.7577 Hunan Road, Pudong New District. Shanghai China,
Shanghai, Shanghai
China, 200000
Tel: 86-21-68172999
Fax: 86-21-58179888