Electrical Product Agents

Share us

GDYZ-30D Metal Oxide Arrester (with Series Gaps) Tester

GDYZ-30D

Description

General Info / Application

GDYZ-30D from HV Hipot Electric is composed of two parts: Control Unit and HV Unit.
It is designed to do breakdown test for lightning arresters with series gaps and TBP over-voltage protectors, which has been widely used in power systems of 35kV and below.

Features
320*240mm LCD screen, and high speed thermal printer.
User-friendly design, intelligent operation, and good anti-interference performance.
Two optional modes for testing: manual and automatic.
Real-time display voltage on high voltage side and current on low voltage side.
Over-voltage and over-current protection, with sound and light alarms.
Zero protection. Test will start only after the instrument has been reset to zero.
Self-diagnostics function, easy to detect errors and solve problems.
Extended functions available, such as remote communication, and calibration interface for voltage divider.
Technical Data

Control Unit
Working voltage: AC 220V ± 10%
Output voltage: AC 0-250V
Output current: 25A
Capacity: 5kVA
Timing range: 0-999s
Environmental temperature: -20°C to 50°C
Voltage accuracy: ≤ ± 2% (F.S)
Current accuracy: ≤ ± 2% (F.S)
HV Unit
Working voltage: 0-200V
Output voltage: 0-50kV
Output capacity: 5kVA
Environmental temperature: -20°C to 40°C
?

MOA tester, surge arrester tester,

Read More

Previous

GDRB-I Transformer Short Circuit and Impedance Tester...

Previous

GDYZ-301 Metal Oxide Arrester (MOA) Tester...

HV Hipot Electric Co.,Ltd

hipot test, switchgear test, MOA test

Address: F/10, Block B7, JinYinTan Modern Enterprise City, Dongxihu District, Wuhan, China,
Wuhan, Hubei
China, 430040

Tel: 0086-27-85568138
Fax: 0086-27-65606183

H5响应式定制设计
26种语言,SEO营销型网站


H5/响应式/营销型企业网站; 26种语言扩展;
覆盖: 英文、法语、德语、西班牙语、葡萄牙语、俄语、阿拉伯语、波斯语、日语、韩语
了解更多