GD6000A is designed to measure the capacitance and dielectric loss factor (tgδ) of electric equipment. It can test grounded equipment, ungrounded equipment, completely-sealed CVT(Capacitive Voltage Transformer), dielectric loss of insulating oil and standard capacitors. It generates the testing voltage by itself, and the frequency is 45-55Hz(or 55-65Hz) to avoid the electromagnetic interference from power frequency, in order to ensure the measuring accuracy.
Features
106*55 LCD display.
Automatical measurement by microcomputer, simple and accurate.
Non-power frequency testing method, to ensure accuracy. Multiple modes for testing,
High capacity of data storage. Test data are saved in time sequence, which can be viewed or exported via U disk.
Convenient for CVT testing, which tests C1 and C2 simultaneously. CVT transformation ratio and voltage angle difference can be tested as well.
High speed of sampling, ensured by digital controlled inverter and sampling circuit.
Multiple protection functions to guarantee safety.
Technical parameters
High Voltage Output: 0.5 ~ 10kV;
Capacity: 1500VA
Accuracy: tgδ: ± (1.0% of the reading +0.04%),Cx: ± (1.0% of the reading+5PF)
Resolution: tgδ: 0.01% Cx: 1pF;
Measuring range: 0.1% < tgδ<50%
3PF < Cx <60000PF
10kV, Cx ≤ 30000PF
5kV, Cx ≤ 60000PF;
Power Supply: AC 220V ± 10% 50 ± 1Hz;
Harmonic meet: ≤ 3%;
Conditions of use: -15 ℃ -50 ℃ Humidity <80%;
Dimensions: 460 (L) × 335 (W) × 340 (H);
Weight: 30 kg;