Laser Equipment

Share us

High Temperature Dual Pipe 4 Row Horizontal Fan Coil Unit ESP 50 pa

EKCW-A

Description

?

?

Dual pipe 4 rows large temperature horizontal concealed fan coil unit ESP 50 pa

?

?

Specifications

?

- - - -
Model
Performance | EKCW
200AA | EKCW
300AA | EKCW
400AA | EKCW
500AA | EKCW
600AA | EKCW
800AA | EKCW
1000AA | EKCW
1200AA | EKCW
1400AA |
Rated air flow (m3/h; under static pressure of 12
Pa, 30 Pa, and 50 Pa) | H | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 |
M | 279 | 418 | 558 | 697 | 836 | 1115 | 1394 | 1673 | 1952 |
L | 170 | 255 | 340 | 425 | 510 | 680 | 850 | 1020 | 1190 |
Rated cooling capacity (W) | Total heating/cooling capacity | H | 2125 | 3385 | 4390 | 4902 | 6207 | 8096 | 10165 | 11066 | 13744 |
Sensible heating/cooling capacity | H | 1233 | 2059 | 2848 | 3353 | 4179 | 5572 | 7125 | 7961 | 9770 |
Rated heating capacity (W) | H | 3576 | 5427 | 6915 | 8335 | 12238 | 13216 | 16587 | 18339 | 22160 |
Rated input power (W) | Static pressure of 12 Pa | H | 32 | 46 | 56 | 73 | 93 | 133 | 164 | 188 | 229 |
Static pressure of 30 Pa | H | 41 | 53 | 72 | 86 | 107 | 142 | 183 | 217 | 239 |
Static pressure of 50 Pa | H | 46 | 65 | 77 | 90 | 115 | 162 | 187 | 227 | 279 |
Working current (A) | Static pressure of 12 Pa | H | 0.15 | 0.21 | 0.26 | 0.33 | 0.42 | 0.61 | 0.74 | 0.85 | 1.04 |
Static pressure of 30 Pa | H | 0.20 | 0.24 | 0.33 | 0.39 | 0.48 | 0.65 | 0.83 | 0.99 | 1.09 |
Static pressure of 50 Pa | H | 0.21 | 0.29 | 0.35 | 0.41 | 0.52 | 0.74 | 0.85 | 1.03 | 1.27 |
Sound dB(A) | Static pressure of 12 Pa | H | 33.5 | 32.5 | 38.5 | 41.5 | 44.5 | 45.0 | 48.0 | 49.0 | 51.0 |
Static pressure of 30 Pa | H | 39.5 | 40.0 | 43.0 | 44.0 | 46.0 | 46.0 | 50.5 | 50.5 | 51.5 |
Static pressure of 50 Pa | H | 42.0 | 43.0 | 45.0 | 46.0 | 47.5 | 48.5 | 50.5 | 52.5 | 53.0 |
Water flow (m3/h) | 0.21 | 0.33 | 0.43 | 0.48 | 0.60 | 0.79 | 0.99 | 1.07 | 1.32 |
Water resistance (cooling) (kPa) | 5 | 13 | 22 | 10 | 16 | 16 | 25 | 20 | 29 |
Water resistance (heating) (kPa) | 4 | 9 | 18 | 8 | 13 | 13 | 20 | 17 | 24 |
Coil | Type | Mechanically expanded quality copper tubes specially designed for air conditioners with shutter-type hyperbolic aluminum fins |
Working pressure | 1.6MPa |
Test pressure | Airtightness test under pressurized water: 3.3 MPa |
Fan | Type | Forward-pitched multi-wing centrifugal fan with double-suction impellers made from zinc-plated steel plates |
Qty. | 1 | 2 | 2 | 2 | 2 | 3 | 4 | 4 | 4 |
Motor | Type | Single-phase? ball-bearing capacitive motor with a high precision and low operation sound |
Qty. | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 |
Power supply | 220V~/50Hz |
Protection grade | IP20 |
Insulation grade | B |
Inlet/outlet water pipe | Pipe diameter | Rc3/4 taper pipe with internal thread |
Condensate water pipe | Pipe diameter | Diameter R 3/4 taper pipe with external threads |
Net weight (no electric heater) | No return air plenum | kg | 11.8 | 14.3 | 16.8 | 17.9 | 19.1 | 28.4 | 31.4 | 34.3 | 41.3 |
With return air plenum | kg | 14.8 | 17.9 | 20.8 | 22.2 | 23.7 | 34.4 | 37.8 | 41.5 | 49.5 |
Electric heater
(optional) | Power supply |   | 220V~/50Hz | 380V/3N~/50Hz |
Electric heating capacity | kW | 1.0/2.0 | 1.0/2.0/3.0 | 2.0/3.0/4.0 | 2.0/3.0/4.0 | 2.0/3.0/4.0 | 3.0/4.0/5.0 | 3.0/4.0/5.0 | 4.0/5.0/6.0 | 5.0/6.0/7.0 |
Net weight (with electric heater) | No return air plenum | kg | 14.9 | 17.5 | 20.5 | 21.8 | 23.2 | 33.4 | 36.6 | 40.1 | 47.8 |
With return air plenum | kg | 17.9 | 21.1 | 24.5 | 26.1 | 27.8 | 39.4 | 43.0 | 47.3 | 56.0 |
- - - -

?

Note:
■ Working conditions for cooling: inlet air temperature - dry/wet bulb 27°C/19.5°C; temperature of inlet/outlet water - 5°C/15°C.
■ Working conditions for heating: inlet air temperature - dry bulb 21°C; inlet water temperature 60°C; water flow - equal to that for cooling
operation.
■ Rated air flow is measured under standard atmosphere using dry coils (dry bulb 20°C).
■ Sound pressure grade and sound level are measured in a semi-silent room as per GB/T 19232-2003.
■ H, M and L represent high, medium and low fan speed respectively.
■ Static pressure refers to outlet static pressure.
■ All performance parameters in the above table are measure with a power supply of 220V~/50Hz.
■ The right/left orientation of connection pipes are exchangeable on site (cooling/heating capacity needs to be multiplied by a correction factor
of 0.93 after exchange).

?

?

?

1.Compact Exterior

?

With a compact, graceful and robust design, this
super-thin unit can be concealed in a small space
inside the ceiling.

?

2.Low Noise


The unit features a forward-pitched low-speed centrifugal fan with wide impellers. The fan has a good
dynamic balance and a stable performance, and minimizes the operation sound while ensuring enough air
flow and the static pressure of outlet air by using efficient sound-dampening and heat-insulation material.

?

3.Efficient and Energy Saving
?

To maximize heat transfer and exchange efficiency, the unit features heat exchange coils made of quality
copper tubes, efficient hyperbolic aluminum shutter fins, precise mechanic tube expansion and a fan with
wide impellers and a high air supply capacity.

?

4.Easy and Flexible Installation
?

The unit features a symmetric design and can be easily installed. The left and right connection pipes are
exchangeable. For units with a return air plenum, the air return mode can be customized.

?

5.Safe and Leakage-proof
?

The condensate water collector are molded as a whole (no welding line or dots) and entirely coated with
fireproof material to prevent leakage. A specially designed pitch on the collector also helps ensure smooth
discharge of condensate water.

?

6.Easy Maintenance


The unit features a single-phase capacitive motor with a low operation sound and a long service life thanks
to a quality precision ball bear that is hermetic, fully lubricated, rustproof and durable. All wires leading out of
the motor are protected against damage using flexible metal tubes.

?

cheap prodocuts, china suppliers,

Read More

Previous

Professional Intelligent Control Modular Water Cooled Scroll Chiller For Schools...

Previous

Centralized Control Water Cooled Scroll Chiller For Air Conditioner...

Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd

Air Cooled Modular Chiller,Air Cooled Screw Chiller,Air Handling Units

Address: Euroklimat Industrial Park, Huangjiang Dongguan Guangdong China,
Dongguan, Guangdong
China, 523766

Tel: 86-769-83660888
Fax: 86-769-83622528

H5响应式定制设计
26种语言,SEO营销型网站


H5/响应式/营销型企业网站; 26种语言扩展;
覆盖: 英文、法语、德语、西班牙语、葡萄牙语、俄语、阿拉伯语、波斯语、日语、韩语
了解更多